Wide Area HVAC controller using WPF and ZigBee Sensor grid

One project I’ve been working on recently revolves around an online controller for a wide area HVAC system. HVAC systems can sometimes be optimized for higher efficiency by monitoring performance in conjunction with environment parameters. Local rules can be established for individual systems based on various temperatures, humidity, and duct configurations. Briefly, a set of HVAC functions consisting of on/off relay switches and thermistors, can be observed from an online monitoring interface. Conversely state changes can be initiated online by issuing a command to a queue. These sensors and relays might be scattered over a relatively large geographic area and in multiple locations inside a commercial building.

It is interesting to connect a macro geospatial world with a micro world, drilling down through a local facility to a single thermistor chip. In the end its all spatial.

Using a simple map view allows drill down from a wide area to a building, a device inside a building, a switch bank, and individual relay or analog channel for monitoring or controlling. The geospatial aspect of this project is somewhat limited, however, the zoom and pan tools used in the map location also happen to work well in the facilities and graphing views.

The interface can be divided into three parts:
1) The onsite system – local base system and Zigbee devices
2) The online server system – standard Apache Tomcat
3) The online client interface – WPF xbap, although svg would also work with a bit more work

Onsite System

The electronically impaired, like myself, may find the details of controller PIC chip sets, relays, and thermistor spec sheets baffling, but really they look more hacky than they are:

Fig 0 – Left: Zigbee usb antenna ; Center: thermistor chip MCP9701A; Right: ProXR Zigbee relay controller

The onsite system is made up of sensors and controller boards. The controller boards include a Zigbee antenna along with a single bank of 8 relays and an addition set of 8 analog inputs. The sensors are wired to the controller board in this development mode. However, Zigbee enabled temperature sensors are also a possibility, just more expensive. See SunSpot for example: http://www.sunspotworld.com/ (Open Source hardware? )

ZigBee is a wifi type communications protocol based on IEEE 802.15.4. It allows meshes of devices to talk to each other via RF as long as they are within about 100-300 ft of another node on the mesh. Extender repeaters are also available. ZigBee enabled devices can be scattered around a facility and communicate back to a base system by relaying messages node to node through an ad hoc mesh network.

The onsite system has a local pc acting as the base server. The local onsite server communicates with an external connection via a internet router and monitors the Zigbee network. ASUS EeePCs look like a good candidate for this type of application. Messages originating from outside are communicated down to the individual relay through the ZigBee mesh, while state changes and analog readings originating from a controller relay or sensor channel are communicated up the ZigBee network and then passed to the outside from the local onsite server.

The local server must have a small program polling the ZigBee devices and handling communications to the outside world via an internet connection. The PC is equipped with a usb ZigBee antenna to communicate with the other ZigBee devices in the network. This polling software was written in Java even though that may not the best language for serial USB com control in Windows. The target system will be Linux based. The ZigBee devices we selected came with the USB driver that treats a USB port like a simple COM port.

Since this was a Java project the next step was finding a comm api. The sun JavaComm has discontinued support of Windows, although it is available for Linux. Our final onsite system will likely be Linux for cost reasons, so this is only a problem with the R&D system which is Windows based. I ended using a RXTX library, RXTXcomm.jar, at http://www.jcontrol.org/download/rxtx_en.html

Commands for our ProXR controller device are a series of numeric codes, for example<254;140;3;1>This series of commands puts the controller in command mode 254, a set bank status command 140, a byte indicating relays 0 and 1 on 3, and bank address 1. The result is relays 0 and 1 are switched to the on position. The commands are issued similarly for reading relay state and analog channels. <254;166;1> for example reads all 8 analog I/O channels as a set of 8 bytes.

Going in prototype mode we picked up a batch of three wire MCP9701A thermistor chips for a few dollars. The trick is to pick the right resistance to get voltage readings in to the mid range of the 8bit or 10bit analog channel read. Using 8 bit output lets us poll for temperature with around .5 degree F resolution.

The polling program issues commands and reads results on separate threads. If state is changed locally it is communicated back to the online server on the next polling message, while commands from the online command queue are written to the local controller boards with the return. In the meantime every polling interval sends an analog channel record back to the server.

Online Server

The online server is an Apache Tomcat service with a set of servlets to process communications from the onsite servers. Polled analog readings are stored in a PostgreSQL database with building:device: bank:channel addresses as well as a timestamp. The command queue is another PostgreSQL table which is checked at each poll interval for commands addressed to the building address which initiated the poll. Any pending commands are returned to the polling onsite server where they will be sent out to the proper device:bank:relay over the ZigBee network.

Two other tables simply provide locations of buildings as longitude, latitude in the wide area HVAC control system. Locations of devices insidebuildings are stored in a building table as floor and x,y coordinates. These are available for the client interface.

Client Interface

The client interface was developed using WPF xbap to take advantage of xaml controls and a WMS mapping interface. Initially the client presents a tabbed menu with a map view. The map view indicates the wide area HVAC extents with a background WMS image for reference. Zooming in to the building location of interest allows the user to select a building to show a floor plan with device locations indicated.

Fig 1 HVAC wide area map view

Once a building is selected the building floor plans are displayed. Selecting an individual device determines the building:device address.

Fig 2 Building:device address selection from facilities floor plan map

Finally individual relays can be selected from the device bank by pushing on/off buttons. Once the desired switch configuration is set in the panel, it can be sent to the command queue as a building:device:bank address command. Current onsite state is also double checked by the next polling return from the onsite server.

Fig 3 Relay switch panel for selected building:device:bank address.

The analog IO channels are updated to the server table at the set polling interval. A selection of the analog tab displays a set of graph areas for each of the 8 channels. The on/off panel initiates a server request for the latest set of 60 polled readings which are displayed graphically. It won’t be much effort to extend this analog graph to a bidirectional interface with user selectable ranges set by dragging floor and ceiling lines that trigger messages or events when a line is crossed.

Fig 4 Analog IO channel graphs

This prototype incorporates several technologies using a Java based Tomcat service online and a Java RXTXcomm Api for the local Zigbee polling. The client interface is also served out of Apache Tomcat as WPF xaml to take advantage of easier gui control building. In addition OGC WMS is used for the map views. The facilities plan views will be DXF translations to WPF xaml. Simple graphic selection events are used to build addresses to individual relays and channels. The server provides historical command queues and channel readings by storing time stamped records. PostgreSQL also has the advantage of handling record locking on the command queue when multiple clients are accessing the system.

This system is in the prototype stage but illustrates the direction of control systems. A single operator can maintain and monitor systems from any locations accessible to the internet, which is nearly anywhere these days. XML rendering graphics grammars for browsers like svg and xaml enable sophisticated interfacesthat are relatively simple to build.

There are several OGC specifications oriented toward sensor grids, http://www.opengeospatial.org/projects/groups/sensorweb. The state of art is still in flux but by virtue of the need for spatial management of sensor grids, there will be a geospatial component in an “ubiquitous sensor” world.